How can I make the drive start immediately after power up or fault reset?

1–2 minutes

In M300 series and C2000 series, set Pr.02-35 = 1

In VFD-E, set Pr.02.05 = 0

With those settings, the drive does not wait for a rising flank, but starts according to the signal level.

Exception: due to compliance with safety requirements and safety certification, the drive will still wait for a rising flank after STO reset before starting the motor