Search

Delta Industrial Automation

Tips & Tricks

Tag

DTB

Temperature controllers: How to Return to Default settings

The ones of you who deal with Delta temperature controllers, sooner or later found on the situation to reset the Temperature controller to default values.

How to do that without using DTCOM?
Please follow the below instructions if you have a DTA or DTB
untitled
In case you have DTD4848 just change the keys [V] & [SET], for [] & [SET].

But what happen with DTC? This device have no buttons.
So If you change the Modus Address, and you do not remember what address you use… you´re in a trouble.

In this case, you have 2 options:
Or you use the LED code of the manual to guess the protocol and address
qqqqqqq

Or just follow the below instructions to take the DTC back to factory defaults:
1. Switch to “RUN, and Power on the device.
untitled1

2. After 5 seconds, the device should show as below picture.
untitled2

3. Switch to Stop and wait until the RUN LED is off
untitled3

4. Switch to RUN and wait for the RUN LED is on again.
untitled4

5. Repeat the steps (3) and (4) three times within 60 seconds, and If everything is OK, all led should switch to ON as below picture.
untitled5

 

This feature is available starting from Firmware v1.5

In case you’re a communication guy, download the attached manual to reset to factory default all Temperature controllers using out software DTCOM.

Default reset by Communication.
DTCOM Software

Please don’thesitate to let us know your Delta Temperature controllers experiences

PLC Link (PLC to Temperature Controllers)

Happy new year 2013 for you all.
We decide to start this new ear with a new chapter of the PLC-Link series, I hope you like it!

As we see on the other chapters PLC to PLC and PLC to VFD, PLC Link is a method to easily communicate with Delta devices based on RS485 Modbus.
Because we already did it PLC and VFD, today we´ll do it with Temperature controllers.

1. Netwrok Structure:
Communication is RS485, so follow the twisted pairs recommendations when possible.
untitled

2. DTC Configuration:
First you have to setup the communication protocol as the PLC (9600,7,E,1 ASCII)
Second, remeber to change to 1 the parameter “Communication write-in selection”

untitled

3. PLC Software:
Step 1 -> Set up communication protocol
Step 2 -> Set the number of register to be read/write (Check manual to understand the D1436 and D1452 special register meaning).
Step 4 -> Select the registers to be read/write (H4700 = Present Value; H4701 = Set Value)
Check the following Table for DTA and DTB
untitled
For DTC or DTD jus follow the DTC manual table
Step 5 -> Enable PLC-Link

Do not hesitate to download the below examples
PLC LINK COM2 (PLC – DTC) and PLC LINK COM2 (PLC – DTA).dvp (Tested by DDC Automation)

Special Thanks to DDC Automation from UK for this example
Let us know your experience

Blog at WordPress.com.

Up ↑